75 kVA 440 Volt to 240 Volt Autotransformer RC75H2-C

Be the first to review this product

Availability: Available for order. Production Time: 3-4 weeks

US$ 3,143.00
OR

Quick Overview

Catalog No.: RC75H2-C
Autotransformer 75 kVA • Three Phase • Primary: 440 Volt • Secondary: 240 Volt
Conductor: Copper

To be confirmed before processing. Shipping time is not included.

US$ 3,143.00

Details

Three phase Autotransformer RC75H2-C has common primary-secondary windings which are not insulated from each other, offers no interference or disturbance isolation between primary and secondary circuits. It is an economical solution but is not suitable for sensitive equipment with electronic and servo components but perfectly suitable for simple motor/heater single or ballanced applications. Strandard 3 phase autotransformer comes without neutral lead, but if you need, please request the neutral lead from "Optional Features" tab.

 

Autotransformer RC75H2-C Winding Schematic:


Wye(Y0) Three phase connection

Preliminary General Drawing. (Dimension, inch).

 

Autotransformer general dimensions


*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.


Full Specification

Catalog No. RC75H2-C
Product Type Autotransformer
Phase Three
Power Rating 75 kVA
Frequency, Hz 60
Vector Group Wye(Y0)
Primary voltage 440 Volt
Primary Max Current, Amps 98
Primary Terminals H1-H2-H3, 6-300MCM
Secondary Voltage 240 Volt
Secondary Max Current, Amps 180
Secondary Terminals X1-X2-X3
Winding Conductor Copper
Temperature Rise, °C 150
Insulation Class 220 (R)
Insulation Level, (B.I.L), kVA 10
Efficiency at 35% Load, % 95.23
ANSI/IEEE Impedance, % 2.5-3.5
Sound Level, dB 50
Standards and Certifications CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type)
CSA certified. File No. LR34493 , Seismic rated for USA zone 4 and Canada zone 6.
UL Listed. File No.E108255.
ISO9001 Quality Certification.
Enclosure Type Nema 3R. General purpose indoor ventilated steel enclosure suitable for dry locations. Sprinkler Proof when angle between sprinkler and opening does not exceed 45°
Weight, Lbs 325.0
Country of Manufacture Canada

Transformer Calculator

Help: To calculate required kVA of the transformer enter Load Amps, Load Volt and press "Required kVA" button. Also you can calculate Current from other two parameters.
Note: Recommended add up to 20% to the calculated kVA