Catalog No.: SC3J-K/EP
3 kVA • Single Phase • Primary: 600 Volt • Secondary: 120/240 Volt
Conductor: Copper

Add Extended warranty to the 1 Year Standard.

+US$ 460.00

Put desire enclosure color code

Please select check box below to request documents and certification, if require.

US$ 686.00

Details

Single phase Epoxy Encapsulated Transformer SC3J-K/EP is sealed in silica sand and resin solid mass, completely enclosing and protecting the core and coil, while significantly reducing audible noise and designed for hazardous environments. It is an isolation transformer where primary winding is physically separated from secondary winding.

 

Epoxy Encapsulated Transformer SC3J-K/EP Winding Schematic:


II Single phase connection

Preliminary General Drawing. (Dimensions in inches).

 

Epoxy Encapsulated Transformer general dimensions


*All information and images presented here is based on preliminary data or design and may be changed without prior notice.
Request Drawing Proof to confirm dimensions from Optional Feature tab, if it is critical.


Full Specification

Catalog No. SC3J-K/EP
Product Type Epoxy Encapsulated Transformer
Phase Single
Power Rating 3 kVA
Frequency, Hz 60
Vector Group II
Primary voltage 600 Volt
Primary Max Current, Amps 5.0
Primary Terminals H1-H2
Primary Terminal Lugs Leads
Primary Voltage Taps none
Secondary Voltage 120/240 Volt
Secondary Max Current, Amps 25 / 12.5
Secondary Terminals X1-X4, Interconnect for: Lower Voltage: X1 to X3 and X2 to X4, or Higher Voltage: X2 to X3
Secondary Terminal Lugs Leads
Winding Conductor Copper
Temperature Rise, °C 115
Insulation Class 180 (H)
Insulation Level, (B.I.L), kVA 10
Efficiency at 35% Load, % 92.96
ANSI/IEEE Impedance, % 3.0-4.0
Sound Level, dB 40
Standards and Certifications CSA Standard C22.2. No.47 Air Cooled Transformers (Dry Type)
CSA certified. File No. LR34493 , UL Listed. File No.E108255.
ISO9001 Quality Certification.
Enclosure Type Nema 3R. Outdoor Non-Ventilated Weather resistant steel enclosure
Weight, Lbs 60.0
Country of Manufacture Canada

Transformer Calculator

Help: To calculate required kVA of the transformer enter Load Amps, Load Volt and press "Required kVA" button. Also you can calculate Current from other two parameters.